This page covers section V (best practices) and section VI (reference
information) of the
[Gen-1 to Gen-1.5 RMU build runbook](/wiki/gen-1-to-gen-1-5-rmu-build/).

The best-practice steps significantly improve the operator
experience — particularly the ability to update firmware on every
server remotely.

> [!WARNING]
> These steps cover foundational hardening only. They do not
> constitute comprehensive security hardening, nor do they replace
> ongoing system maintenance. Each node provider is responsible for
> their own secure and well-maintained environment.

## A. Proxmox security (Recommended)

### Enable Proxmox firewall — Datacenter level

1. In the Proxmox WebUI, select **Datacenter** in the left panel.
2. In the middle panel, scroll to **Firewall** > **Options** and
   select the top **Firewall** configuration option in the main
   panel. Click **Edit** at the top of the list.
3. In the dialog, tick the **Firewall** box and click **OK**.

### Enable Proxmox firewall — RMU level

1. Select the RMU in the left panel.
2. In the middle panel, scroll to **Firewall** > **Options** and
   select the top **Firewall** configuration option in the main
   panel. Click **Edit**.
3. In the dialog, tick the **Firewall** box and click **OK**.

### Disable RPCBIND

1. Select the RMU in the left panel.
2. Click **Shell** in the top right.
3. Run these commands one at a time:

   ```bash
   systemctl disable rpcbind.target
   systemctl disable rpcbind.socket
   systemctl disable rpcbind.service
   systemctl stop rpcbind.target
   systemctl stop rpcbind.socket
   systemctl stop rpcbind.service
   ```

## B. Install RACADM tool on RMU (Optional, Dell nodes)

This section applies to sites with Dell node machines. Installing
RACADM lets the RMU access the iDRAC interface on Dell servers — for
example, to update iDRAC settings or open an emergency console
shell.

1. In the Proxmox WebUI, select the RMU in the left panel and click
   **Shell** in the top right.
2. Execute the following commands:

   ```bash
   echo 'deb http://linux.dell.com/repo/community/openmanage/11010/jammy jammy main' | sudo tee -a /etc/apt/sources.list.d/linux.dell.com.sources.list
   wget https://linux.dell.com/repo/pgp_pubkeys/0x1285491434D8786F.asc
   apt-key add 0x1285491434D8786F.asc
   apt-get update
   apt install gpg libssl-dev -y
   apt install srvadmin-idracadm8 -y
   ```

3. To allow the Teleport server to forward the iDRAC web interface,
   disable the SSL header check on each Dell node. Run this once per
   Dell node from a shell on the RMU:

   ```bash
   racadm -r 10.10.100.55 -u root -p <password> set idrac.webserver.HostHeaderCheck 0
   ```

   > [!NOTE]
   > `<password>` is the iDRAC/BMC password for the Dell node. If
   > the password has not been reset, it is on the pull-out tab on
   > the front face of the server. If it has been reset and the
   > current password is unknown, you must use a physical console
   > ("crash cart") and boot the server into iDRAC recovery mode to
   > reset it. See [iDRAC Access and TSR Logs](/wiki/idrac-access-and-tsr-logs/).

## C. Dell OpenManage Enterprise (Recommended, Dell nodes)

Dell OpenManage Enterprise (OME) communicates with the Baseboard
Management Controllers (BMCs) of your nodes. It can discover the
iDRACs of Dell servers and apply firmware updates remotely.

### Create the OME VM

1. From the main Proxmox page, click **Create VM**.
2. Tick **Advanced** and **Start at boot**. Configure:
   - **VM ID**: `123`
   - **Name**: `<dc>-ome`
   - **Start/Shutdown Order**: `10`

   Click **Next**.
3. On the OS tab, select **Do not use any media**. Set **Type** to
   `Other`. Click **Next**.
4. On System: ensure **Graphic card** is `Default`,
   **SCSI Controller** is `VirtIO SCSI single`, **Machine** is
   `Default (i440fx)`, **BIOS** is `Default (SeaBIOS)`. Click
   **Next**.
5. On Disks: **Bus/Device** `IDE` and `0`, **Storage** `local-zfs`,
   **Disk size (GiB)** `8`, tick **Backup**, **Async IO**
   `Default (io_uring)`. Click **Next**.
6. On CPU: **Sockets** `1`, **Type** `X86-64-v2-AES`, **Cores** `8`.
   Click **Next**.
7. On Memory: **Memory (MiB)** `16767`, **Minimum memory (MB)**
   `2048`. Click **Next**.
8. On Network: **Bridge** `vmbr1`, **Mode** `Intel E1000`, untick
   **Firewall**. Click **Next**.
9. Do **not** tick **Start after created** — the OME image still
   needs to be mapped to a disk. Click **Finish**.

### Download and import OME

1. Open a shell console on the RMU and download the OME virtual
   image:

   ```bash
   wget --user-agent="Mozilla" -O ome.zip 'https://dl.dell.com/FOLDER07474001M/1/openmanage_enterprise_kvm_format_3.6.1.zip?uid=c802e350-6536-4f28-7a66-93b4f844cd30&fn=openmanage_enterprise_kvm_format_3.6.1.zip'
   ```

2. Unzip the download:

   ```bash
   apt update && apt install unzip -y
   unzip ome.zip
   ```

3. Import the QCOW2 image into the OME VM's storage:

   ```bash
   cd appliance/qemu-kvm/
   qm importdisk 123 openmanage_enterprise.qcow2 local-zfs
   ```

4. Configure the imported disk as the boot disk:
   - Select the **OME** VM in the left panel.
   - Click **Hardware**.
   - Double-click **Unused Disk**.
   - Set **Bus/Device** to `VirtIO Block`. Click **Add**.
   - Click **Options**, then double-click **Boot Order**.
   - Move the device described as `local-zfs:vm-123-disk-1…` to
     position 1 and tick **Enable** next to it.
   - Untick the enable box for all other boot devices. Click **OK**.
5. Select the **OME** VM and start it.

### Configure OME

1. Select the **OME** VM and click **Console**. Allow time for the
   first boot.
2. On EULA, select **Accept**.
3. Select your keyboard type.
4. Set a non-trivial password and store it in your password manager.
   Tab to **Apply** and press Enter.
5. Use the arrow keys to scroll to **Set Networking Parameters** and
   press Enter.
6. Press Enter on the available network adapter.
7. Enter the password you just created. Tab to **Continue** and
   press Enter.
8. Configure the network:
   - **IPv4 Address (Static)**: `10.10.100.23`
   - **Static Gateway**: `10.10.100.1`
   - **Static Subnet Mask**: `255.255.255.0`
   - **Static Preferred DNS server**: `1.1.1.1`

   Use the arrow keys to navigate to DHCP, then Tab into the
   editable text fields.
9. Select **Apply**.
10. Re-enter your non-trivial password and select **Continue**.

### Share OME with Teleport

1. Open a shell on the RMU server and edit `/etc/teleport.yaml`.
2. Add the following section under the `app_service -> apps`
   stanza, matching the indentation of the previous `name: bo1-rmu`
   section. Replace `bo1` and `.dfinity.network` with the
   placeholders used earlier in the runbook:

   ```yaml
   - name: bo1-ome
       uri: https://10.10.100.23:443
       public_addr: "bo1-ome.teleport.bo1.dfinity.network"
       insecure_skip_verify: true
       rewrite:
         redirect:
         - "10.10.100.23"
         - "bo1-ome.teleport.bo1.dfinity.network"
       labels:
         dc: "bo1"
   ```

3. Reload the Teleport service:

   > [!WARNING]
   > If you are accessing the RMU shell via Teleport, your
   > connection will be disconnected when the service restarts.

   ```bash
   systemctl restart teleport
   ```

### Configure the OME web GUI

1. From the Teleport Resources page, find the OME tile and select it
   to open the web UI.
2. Sign in. The default user is `admin` with the password set during
   OME installation.
3. Click **Initial Settings** under Step 1.
4. Expand **Time Configuration** and set the timezone — UTC is
   recommended (DFINITY uses UTC; if you operate more than one data
   center, a single timezone keeps cross-DC reasoning simpler).

### Discover your nodes

1. On Step 2 click **Discover Devices** to open the Create Discovery
   Job dialog.
2. Under **Device Type**, select **Server**. Ensure **Dell iDRAC**
   is selected, click **OK**.
3. Under **IP/Hostname/Range**, enter `10.10.100.53-10.10.100.99`.
4. Under **Services API Credentials**, enter the iDRAC username and
   password. If iDRACs use different passwords, click **Add** and
   add each IP individually.
5. Click **Finish**.

   > [!TIP]
   > If not all nodes are discovered on the first attempt, narrow
   > the range or add each host separately with its own credentials.

6. Monitor the discovery from **Monitor** > **Jobs** in the top
   navigation bar.

### Create a baseline

1. Click **Configuration** > **Firmware/Driver Compliance**.
2. Click **Create Baseline**.
3. In the dialog, click **Add** next to **Catalog**.
4. Enter a name for the catalog (e.g. `Dell Catalog`).
5. Ensure **Latest Component versions on Dell.com** is enabled.
   Click **Finish**.
6. Enter a baseline name. Including the `<dc>` code is recommended.
   Click **Next**.
7. Click **Select Devices**.
8. Click the small box and tick **Across all pages** to select all
   devices. Click **OK**.
9. Click **Finish**.

### Applying firmware updates

#### Single server

1. Click **Devices**.
2. Click the IP address in the **Name** column to open a single
   device.
3. Click **Firmware/Drivers**.
4. Select the baseline you created earlier in the drop-down.
5. Tick the firmware updates you wish to apply.
6. Click **Update**, then **Update Now**.
7. Set **Reboot Server immediately** to
   `Graceful Reboot with Forced Shutdown`.
8. Tick **Reset idrac**.
9. Tick **Clear Job Queue**.
10. Click **Update**.

#### Multiple servers

1. Click **Configuration** > **Firmware/Driver Compliance**.
2. Tick the box next to the baseline you created earlier.
3. Click **Check Compliance**.
4. Click **View Report**.
5. Tick the boxes next to the servers you wish to update.
6. Click **Make Compliant**, then **Update Now**.
7. Set **Reboot Server immediately** to
   `Graceful Reboot with Forced Shutdown`.
8. Tick **Reset idrac**.
9. Tick **Clear Job Queue**.
10. Click **Update**.

## D. Update firmware on SuperMicro nodes (Recommended)

1. Open and log in to the BMC of the SuperMicro node you wish to
   update.
2. Click **System** > **FRU Reading**.
3. Note the **Board Product Name** on this page.
4. Search the SuperMicro firmware page for the latest BMC firmware
   for that board:
   [supermicro.com/support/resources/bios_ipmi.php?type=BMC](https://www.supermicro.com/support/resources/bios_ipmi.php?type=BMC).
5. Once you locate your motherboard, click **Resources**.
6. Under **Software**, click **BMC Firmware**.
7. Download and extract the firmware archive.
8. In the BMC, click **Maintenance** > **Firmware Update**.
9. Click **Enter Update Mode**.
10. Click **Yes** in the confirmation dialog.
11. Click **Upload Firmware**.
12. Click **Yes** in the confirmation dialog.
13. **Untick** **Preserve Configuration** (unchecking this restores
    the BMC's factory default settings).
14. Click **Start Upgrade**.

    > [!NOTE]
    > After the firmware update completes, clear the cache of any
    > browser that previously connected to that BMC web console.

## E. Enable remote access to server console (Recommended, Dell nodes)

These steps depend on
[Dell OpenManage Enterprise](#c-dell-openmanage-enterprise-recommended-dell-nodes)
being installed.

### Allow iDRACs to be browsable through Teleport

1. In OME, click **Devices** in the top navigation bar.
2. Click the checkbox in the middle of the screen, then **Across all
   pages** to select every node.
3. Click the **More Actions** drop-down and select **RACADM CLI**.
4. In the **Arguments** box, enter:

   ```text
   set idrac.webserver.HostHeaderCheck 0
   ```

5. Confirm that all your nodes are listed under **Selected devices**.
6. Click **Finish**.
7. Click **Monitor** in the top navigation bar, then **Jobs**.
8. Find the **Remote command line** job and click it. Click **View
   Details**. Selecting any individual node shows execution details
   on the right.

### Add Teleport entries for BMC/iDRAC access

1. *(No longer needed for the `idrac.sh` script)* On the MaaS
   server, in a shell (access via Teleport MaaS SSH access as user
   `admin`), configure the `maas` command:

   ```bash
   sudo apt install jq -Y

   sudo maas apikey --username dfnadmin
   stuff:stuff:stuff

   maas login maas http://localhost:5240/MAAS
   API key (leave empty for anonymous access):  <enter the api key above>
   ```

2. Rename the existing Teleport configuration to a base file:

   ```bash
   sudo mv /etc/teleport.yaml /etc/teleport.yaml-base
   ```

3. Save the following script as `idrac.sh` on the MaaS server:

   ```bash
   #! /usr/bin/env bash

   # Start with the base /etc/teleport.yaml file and add
   # the iDRAC device entries to it.

   if [ -r /etc/teleport.yaml-base ] ; then
     cp /etc/teleport.yaml-base /etc/teleport.yaml
   else
     echo "/etc/teleport.yaml-base not found.  Aborting."
     exit 1
   fi

   # Add a comment at the end of the base configuration to
   # indicate where the automagic script configuration starts.
   echo "### Automation added below ###" >> /etc/teleport.yaml

   echo "Finding iDRAC devices..."

   # Only pull out the DHCP Dynamic Range (from MaaS)
   grep '10.10.100.[56789][0-9]' /var/log/syslog | grep DHCPACK |

   while read a a a a a a a IP a a NAME stuff
   do
     echo "$NAME $IP"
   done |

   # Get rid of the duplicates
   sort -u |

   # Walk the list of NAME/IP and clean up the values
   while read NAME IP
   do
     # Sanitize the NAME variable by removing the '()' and lower casing it
     NAME="$(echo $NAME | sed -e 's/[()]//g' | tr [:upper:] [:lower:])"
     echo "$NAME $IP"
   done |

   # Add the host to the /etc/teleport.yaml
   while read NAME IP
   do
     echo "Adding ${NAME} to /etc/teleport.yaml ..."
     tee -a /etc/teleport.yaml <<EOF
     - name: ${NAME}-idrac
       uri: https://${IP}:443
       #public_addr: ""
       public_addr: "${NAME}-idrac.teleport.<dc>.dfinity.network"
       insecure_skip_verify: true
       rewrite:
         headers:
         - "Host: ${NAME}-idrac.teleport.<dc>.dfinity.network"
         - "Origin: https://${NAME}-idrac.teleport.<dc>.dfinity.network"
       labels:
         dc: "<dc>"
         type: "bmc"
   EOF
   done
   ```

4. Edit `<dc>` in the script to match your data center code, save,
   and execute it:

   ```bash
   chmod +x ./idrac.sh
   sudo ./idrac.sh
   ```

5. When the script completes, reload Teleport:

   ```bash
   sudo systemctl reload teleport
   ```

6. Within a few minutes, your iDRAC devices appear in the Teleport
   web UI.

## F. Enable GUI access to OPNsense devices (Recommended)

This section adds Teleport entries for managing the OPNsense
firewalls through the web GUI.

### Add IPv6 host entries

Add the IPv6 address of each OPNsense device to the end of the
`/etc/hosts` file:

```bash
<IPv6_of_1st_OPNsense_device> br2-fw01
<IPv6_of_2nd_OPNsense_device> br2-fw02
```

### Add Teleport entries for the OPNsense firewalls

1. Edit `/etc/teleport.yaml` on the RMU and add:

   ```yaml
   - name: <dc>-fw01
     uri: https://[<IPv6_of_1st_OPNsense_device>]:443
     public_addr: "<dc>-fw01.teleport.<dc>.<domain>"
     insecure_skip_verify: true
     rewrite:
       redirect:
       - "[<IPv6_of_1st_OPNSense_device>]"
       - "<dc>-fw01.teleport.<dc>.<domain>"
     labels:
       dc: "<dc>"

   - name: <dc>-fw02
     uri: https://[<IPv6_of_2nd_OPNSense_device>]:443
     public_addr: "<dc>-fw02.teleport.<dc>.<domain>"
     insecure_skip_verify: true
     rewrite:
       redirect:
       - "[<IPv6_of_2nd_OPNsense_device>]"
       - "<dc>-fw02.teleport.<dc>.<domain>"
     labels:
       dc: "<dc>"
   ```

2. Reload the Teleport service:

   ```bash
   sudo systemctl reload teleport
   ```

3. The OPNsense GUIs are now visible in Teleport, and clicking each
   one opens the OPNsense login page.

## Reference: internal network layout

All Gen-1 data centers are recommended to use the following private
static IP addresses for the management network.

The MaaS DHCPv4 BMC range is `10.10.100.50-10.10.100.99`. This
allows for an RMU, fw01, fw02, and 46 IC BMC addresses.

| Name | "Management" Private IPv4 `10.10.100.0/24` | "BMC" IPv4 `10.10.100.0/24` | Management Public IPv4 | Public IPv4 Uplink (`/28`) | Public IPv6 Uplink | "Delegated" IPv6 Prefix (`::/64`) | Notes |
| --- | --- | --- | --- | --- | --- | --- | --- |
| Upstream Provider IPv6 Uplink Default Router |  |  | `${MGMTIPV4}+1` | `${PUBLICIPV4}+1` | `${UPLINKIPV6}::1` |  | Upstream provider may use something like VRRP on `:2`/`:3` |
| RMU | `10.10.100.1` | `10.10.100.50` | `${MGMTIPV4}+2` |  |  | `${DELEGATED}::EIP64` |  |
| fw01/router01 | ? | `10.10.100.51` |  |  | `${UPLINKIPV6}::4` | `${DELEGATED}::1` |  |
| fw02/router02 or bn01 | ? | `10.10.100.52` |  |  | `${UPLINKIPV6}::5` | `${DELEGATED}::2` |  |
| msw01 | `10.10.100.10` |  |  |  |  |  |  |
| sw01 | `10.10.100.11` |  |  |  |  |  |  |
| sw02 | `10.10.100.12` |  |  |  |  |  |  |
| sw03 | `10.10.100.13` |  |  |  |  |  |  |
| sw04 | `10.10.100.14` |  |  |  |  |  |  |
| teleport | `10.10.100.22` |  |  |  |  | `${DELEGATED}::EIP64` |  |
| maas | `10.10.100.20` |  |  |  |  |  |  |
| monitoring | `10.10.100.21` |  |  |  |  |  |  |
| ome | `10.10.100.23` |  |  |  |  |  |  |
| iDRAC / BMC |  | `10.10.100.53-10.10.100.99` |  |  |  | `${DELEGATED}::EIP64` |  |
| Unallocated |  | `10.100.100.100-10.100.100.254` |  |  |  |  |  |

## Reference: RMU cabling

If this is a Gen-1 site that already has a SuperMicro RMU, the
cabling should already be in place.

> [!NOTE]
> This cabling is not mandatory, but it is the recommended layout.

| Device ID | Network/Port | Device ID | Port |
| --- | --- | --- | --- |
| CoreSite Fiber Internet | WAN | mm1-MSW01 | 51 |
| mm1-RMU | WAN | mm1-MSW01 | 2 |
| mm1-MSW01 (Dell 3048) | Management | mm1-MSW01 | 3 |
| mm1-SW02 (Dell 4148) | Management | mm1-MSW01 | 4 |
| mm1-RMU | LOM | mm1-MSW01 | 6 |
| mm1-FW01 | Management | mm1-MSW01 | 7 |
| mm1-FW02 | Management | mm1-MSW01 | 8 |
| mm1-RMU | Management | mm1-MSW01 | 10 |
| mm1-RMU | VLAN 66 | mm1-SW02 | 20 |
| mm1-RMU | LAN | mm1-SW02 | 52 |
| mm1-FW01 | LAN | mm1-SW02 | 53 |
| mm1-FW02 | LAN | mm1-SW02 | 54 |

## Reference: checking number of internal drives

1. Ensure the RMU is powered off.
2. Connect a crash cart to the RMU. Connect both the VGA and
   keyboard.
3. Power it on and press the **Del** key repeatedly to enter System
   Setup (BIOS).
4. Use the arrow keys to scroll over to **Save and Exit**.
5. Under **Boot Override**, count the number of hard drive entries.

   > [!NOTE]
   > Normally an RMU has one or two drives in total.

6. Power off the server.

## Related

- [RMU build — Gen-1.5](/wiki/gen-1-to-gen-1-5-rmu-build/) — the parent runbook index.
- [RMU Build: MaaS Setup](/wiki/rmu-build-maas/) — the previous section.
- [iDRAC Access and TSR Logs](/wiki/idrac-access-and-tsr-logs/) — used when an iDRAC password needs recovery.
- [Updating Node Firmware](/wiki/updating-node-firmware/) — companion runbook for routine firmware updates.